详情咨询艾默生服务热线:400-619-2138Thank you for purchasing our product. Observe the warnings on the machine and manual strictly and properly keep the manual. Do not operate the UPS before read safety notes and operation instructions.
INDEX
1.1 Description of the Symbols
Chapter 2 Product introduction
3.3 Procedure of UPS cable connection
3.5 Connected to the computer interface
3.6 Installation of intelligence card
3.9.1 Dust-proof network(optional)
4.1.3 LED operation panel explanation
4.2.2 DC without utility power
4.4 LED panel light and display
4.5 LCD Panel light and display :
4.6 LCD panel lcd display content
6.1 LED Panel trouble shooting
6.2 LCD panel trouble shooting
Appendix A Rack mounted battery pack
Appendix B intelligent slot (Optional)
Chapter 1 Safety Introduction
1.1 Description of the Symbols
All of the symbols as listed in the table below maybe used in this manual .This symbols are used for reminding users of safety notes for installation, operation ,and maintain.
Symbol & Description |
|
Symbol |
Description |
|
Caution,danger |
|
Danger electric shock |
|
Alternating current(AC) |
|
Direct current(DC) |
|
Protective ground |
|
Recycle |
|
Do not dispose with ordinary trash |
1.2 Safety Notes
1.Read this manual carefully and thoroughly before operation the UPS and save this manual properly for reference.
2. When operating,please pay attention to all the alarming marks and operate in required.
3. Avoid direct sunlight, rain, or in a wet environment to use this equipment
4.This UPS can not be installed near the heat source area, or an electric heater, furnace and other similar equipment .
5.When placing UPS,leave a distance around to ensure ventilation. When installing,please refer to the instructions
6.Wipe with dry goods when cleaning.
7. In the event of fire occurring in the vicinity, please use dry powder fire extinguishers. The use of liquid fire extinguishing agents cause electric shock.
1.3 Electric safety
1. Before power, make sure is properly grounded, and check the wiring and the battery polarity is connected correctly
2. When the UPS need to move or re-wiring, disconnect the AC input power and to ensure that UPS is completely shut down, otherwise the output may still be charged, and there is the risk of electric shock
3. Please use our attachments and accessories specified.
4. To comply with EMC requirements, UPS's output line length should be within 10 meters
1.4 Battery safety
1. Battery life shorten with arising ambient temperature. Replace battery regularly can ensure it works and to ensure adequate back-up time.
2. Battery maintenance only be operated by professional personel who have barrtey knowledge.
3. There is risk of electric shock and short circuit the battery current danger. To avoid electric shock injury accident in the replacement battery, please observe the following warning:
A. Do not wear watches, rings or similar metal objects
B. Use insulated tools
C.Wear rubber boots and gloves
D. Do not put metal tools or similar metal parts on the battery
E. Before the separation of the battery connection terminals,you must first disconnect the load on the battery.
4.. Do not expose of batteriy to the fire, they may explode.and endanger safety
5. Non-professionals do not open or mutilate the battery, because batteries contains electrolyte acid and other hazardous substances, which will cause skin and eye damage. If you accidentally come into contact with the electrolyte, wash with plenty of water immediately and go to the hospital
6. Do not short the positive and negative of the battery electrode, otherwise, it may result in electric shock or fire.
1.5 Maintenance
1. Method of using the environment and save the life and reliability of this product have an impact,do not work in the following environments:
A. Exceed the specfications (temperature 0℃ ~ 40℃, relative humidity 20% ~ 90%) of the high and low temperatures and wet places
B. Vibration or shocks places
C. Metallic dust, corrosive substances, salt and flammable gases
2. If the extended period of time is not used, must be UPS (without batteries) stored in a dry environment, the storage temperature range: -25℃ ~ +55℃. UPS power, you must warm up the ambient temperature above 0℃ and keep 2 hours
Chapter 2 Product introduction
2.1 Product introduction
This series of UPS is an advanced on-line uninterruptible power supply sine wave,with bypass maintenance switch and parallel redundant functions. It can provide reliable, high-quality AC power for your precision equipment. It can be widely used from computer equipment ,communication systems to industrial automation equipment. Because of its on-line design, different from the reserve-type UPS, constantly adjusting its input voltage, filter.When the utility power break off, it will have no time to break from the backup battery to provide backup power. In the case of overload or inverter failure, UPS will switch to bypass mode, the utility power supply. If the elimination of overload, UPS will automatically switch back to inverter power supply status.
Any of the above models, is divided into Standard and Professional Edition for users to choose.Professional, relative to the Standard Edition, increases EPO switch, manual maintenance bypass switch.
2.2 Model type
This series UPS model type show below.
(3) (x)K [S] [R] [X]
(3) With 3 means three phase input ,or single phase input。
(x) means capacity of ups, 1, 2, 3 for this manual product. K means capacity of UPS, KVA
[S] With S means Long backup time type , UPS can connect with external batteries. And without S means ups is standard backup time type.
[R] With R means Rack mounted, without R is Tower mounted.
[X] With X means LCD display panel and without X means LED display panel.
model |
discription |
C6K[R][X] |
6KVA UPS, RACK OR TOWER, LED OR LCD, with inner batteries |
C6KSR[R][X] |
|
C10K[R][X] |
10KVA UPS, RACK OR TOWER, LED OR LCD, with inner batteries |
C10KS[R][X] |
6KVA UPS, RACK OR TOWER, LED OR LCD, external batteries |
3C10KS[R][X] |
10KVA UPS, RACK OR TOWER, LED OR LCD, external batteries |
3C15KS[R][X] |
15KVA UPS, RACK OR TOWER, LED OR LCD, external batteries |
3C20KS[R][X] |
20KVA UPS, RACK OR TOWER, LED OR LCD, external batteries |
note:For C6KR,C10KR, battery pack needed, please refer to appendix A。
2.3 UPS appearance
2.3.1 Front panel
1 Computer Interface
2 Intelligent slot
3 Fan
4 Parallel card cover ( optional )
5 Input breaker
6 Maintain switch cover, ( Maintain switch is optional )
7 Wire terminal cover
8 Wire fix
9 EPO (Optional)
2.4 Specification
2.4.1 Electric specification
model Item |
C6K |
C6KS |
C10K |
C10KS |
3C10KS |
3C15KS |
3C20KS |
|
Power Rating |
6KVA/4.8KW |
10KVA/8KW |
15KVA/12KW |
20KVA/16KW |
||||
AC IN |
Wire method |
Single phrase or three phase & earth ground |
||||||
Rated Voltage |
220VAC |
380VAC |
||||||
Rated Freq |
50Hz |
|||||||
Voltage Range |
120~275VAC±5 |
|||||||
Frequency Range |
(45~55)±0.5Hz |
|||||||
Bypass Range |
80VAC×(1±5%)~285VAC×(1±5%) |
|||||||
BAT |
Rated Bat Voltage |
192VDC(Optional 240V) |
||||||
Battery capacity*Quantity |
12VDC*16(Optional 20节) |
|||||||
AC OUT
|
Output system |
|||||||
Output voltage |
220VAC±3% |
|||||||
Output frequency |
46-54Hz(Line normal) 50Hz±1%(Line abnormal) |
|||||||
Dynamic voltage transient range |
<5% |
|||||||
Dynamic transient restore |
< 60ms |
|||||||
Waveform |
Sine Wave THD<3%(linear load) Sine Wave THD<8%(nonlinear load) |
|||||||
Input power factor |
0.8 |
|||||||
Overload capability |
105-125% 30s to bypass |
|||||||
Communications |
RS232(turn to 485), Intelligent slot |
2.4.2 Measurement and Weight
model |
Size W*H*D(mm) |
wight (kg) |
C6KS |
248×460×500 |
20 |
C10KS |
248×460×500 |
22 |
C6K |
248×620×500 |
57 |
C10K |
248×620×500 |
67.5 |
3C10KS |
248×620×500 |
27 |
3C15KS |
248×620×500 |
35 |
3C20KS |
248×620×500 |
35 |
C6K(S)R |
20 |
|
C10K(S)R |
22 |
2.4.3 Environmental
ITEM |
Normal range |
Ambient temperature |
-10℃~ +40℃ |
Environment humidity |
0~90%,no condensation |
Altitude |
Lower than 1000m: no derating Over 1000m :1% derating for every 100m rise |
Storage temperature |
-15℃~+45℃ |
2.4.4 EMC
ITEM |
Standard |
Level |
ESD |
IEC61000-4-2 |
LEVEL4 |
RS |
IEC61000-4-3 |
LEVEL3 |
EFT |
IEC61000-4-4 |
LEVEL4 |
SURGE |
IEC61000-4-5 |
LEVEL4 |